SEW-Taiwan

Sew 4153 IN

FEATURES
● Microprocessor-controlled.
● Measures Insulation Resistance, voltage (AC-DC) measurements
   with automatic hold facility, diode, ohm, and continuity with a short
   circuit current of minimum 220mA.
● Auto-off function.
● Energy conservation feature.
● Ener-Save™ limit the test duration to about 10 Seconds.
● Quick Test and EnerSave™ are unique features. Both saves energy.
● No moving parts. All calibration are saved internally in a non volatile memory.
● Easy calibration at any facility around the world.
● Operates with rechargeable batteries, alkaline or low cost general purpose batteries.
● Low cost maintenance, calibration, and ownership.
● Complies to all the latest regulations, including UK.
 
  SPECIFICATIONS
     
Insulation Test    
Test voltage (DC V)
and Measuring ranges
250V / 0.2M~2G
500V / 0.2M-4G
1000V / 0.2M-8G
Output voltage @ 1mA Rated test Voltage +10% Max
Accuracy 0.2M~4G : ±3%rdg  
4G
~8G : ±5%rdg
When voltage is constant,
Current is limited at
1.2mA
Short circuit current 4mA Max.
Continuity    
Measuring range 0.01-1999
Accuracy 0.01-100 : ±1.0%rdg    
100-300
: ±1.5%rdg    
300-1999
: ±2.0%rdg
Short circuit terminal
current
>220mA
Open circuit terminal
voltage
5V dc
Resolution ±2 counts
Voltmeter    
AC voltage (Auto) 0-700V
DC voltage (Auto) 0-950V
Accuracy ±1.5% rdg
Resolution ±1V
Protections    
Over load 700V
(between all terminals)
Over voltage Class III-700V towards ground
Fuse 500mA 250V, (5 × 20mm), HBC, Fast Blow
General    
Display 2 lines × 16 characters LCD
Auto-null threshold 5
Buzzer threshold 3
Fast test 10Sec
Long test 60Sec
With PI and DAR
test function
10Min
Load battery test current About 300mA
Operating temperature 0°C to 40°C not in full sun
Storage temperature -10°C to 50°C
Dimensions
(with housing front cover)
250(L) × 190(W) × 110(D)mm 
Weight
(battery included)
Approx. 1460g   
Power source 1.5V (AA ) × 8
Safety standard EN 61010-1 CAT III 600V
EN 61326-1

Location