Live Wire Asia Pacific Arc Chaser™ SSTDR Cable Tester

Capable of finding faults (Opens, Shorts, Arc Faults) on fully energized cables up to 600 Volts; Monitor live cables for intermittent conditions.

Features : 

EFFICIENCY
SSTDR inside
SSTDR stands for Spread Spectrum Time Domain Reflectometry, which is LiveWire's patented technology. The technology reduces maintenance, troubleshooting, and/or monitoring costs, increases system reliability, and can extend the useful life of systems and structures by providing accurate monitoring of system health environments. 

On the other hand, Time Domain Reflectometry (TDR) methods were not able to locate the tiny intermittent faults left after an arc fault event because the impedance discontinuity was too small to create a measurable reflection. LiveWire recognized this lapse in technology and determined that if an electrical fault could be found during the few milliseconds the arc occurs, it would be an actual short circuit which returns plenty of reflected power! This is the concept that led to the development of SSTDR at LiveWire.
Fault Location
Gives you Quick picture of existing cable faults and condition, and shows the distance to shorts or open faults at the same time. Be able to test multiple kinds of electrical faults up to 12,000gt. Locate shorts, open,and intermittent arc fault with accuracy to fault of better than 1%.
Cable Length
Input VOP values or choose the cable type in the system menu, and get the length of cables in no time. Be able to measure coax, Cat6, and any other twisted cables.
Dual Mode
The test system can pinpoint and record the location of these conditions on both live(operational) and dead systems. As a result, discovering cable events which can only be shown under load has become possible and easy, and the wiring maintenance crews can quickly locate and repair wiring damage, reducing maintenance costs and maximizing operational readiness.
Work on Energized Systems up to 600V
Being able to test on live(operational) and systems, the device is capable of finding faults (Opens, Shorts) on fully energized cables up to 600 Volts, which also means that it can Meet full international requirements for working on energized cables.
Long Lasting Power
Field work can be really time consuming and tiring, and we understand that it is annoying to find that your device power is out or need to change batteries during the working process. With 3rd generation rechargeable lithium ion batteries, the device is capable of 8 to 10 hours of continuous use.
SD Card
Saving and transferring your testing datas can never be more easier.With the Kingston SDHC class 4 SD card in the device, you can save all the data sheets in it, and transfer them into your PC when you need to, just like using a digital camera.

INTERFACE
Full Color Touch Screen
There are many lighting environments in the field, and we understand that the traditional screen display can be so difficult to view in such environment. With full color screen display, it is much more easier to navigate your device in all lighting environments. To make it more intuitive to operate the device, touch screen is applied. No more struggles with the buttons, the touch screen function makes it easier and faster.
Live Event Detection
Detect, locate, and characterize cable faults, with ability of continuous monitoring for intermittent faults.
Build-in List
Every type of cable has different VOP value, and test frequency. We have all the most common setting values in the device, so all you have to do is click and choose the type of cable and the right value set. There is no need for memorizing the or looking up for numbers, let the device help you and save your time.
Graphic Results
To make the device more user-friendly, we provide not only text format but also graphical result of the tests. Both the results can be transferred into PDF file and saved into SD card.
PDF File Transfer
The result can be transferred into PDF files right after the testing process. On the device, you can easily type and edit the name of the file, leave comments, and the date&time will automatically be saved in the file as well. In other words, once your field works in done, your paper reports can be finished at the same time, all you have to do is go back to the office and print them out.
Tone Generation
Built in tone track function helps you to trace the signal of cables without the need of other extra equipments. With this function you can easily find the cable that you test on among the complex cable systems, save your time for the main issue and acquire better working efficiency.

OTHER FEATURE
.Compact Form Factor:Usable in tight space environments
.Benchtop, Handheld, or Hung Up:Easy to use for field flight line and production work
.Uses Modular Cable Interfaces:Can connect to many different types of systems
.Waterproof/Shock Resistant Transport Case:Protects equipment in harsh conditions
.Upgradeable Firmware:Stay up to date with cable settings, features and enhanced software upgrades.
 
Specification : 
TECHNICAL
Technology SSTDR U.S. Patents and Patents Pending
Maximum Range 12,000 ft (3,657m) at .999 VOP
Maximum testable cable length varies with VOP and cable type.
VOP (%) with 3 digit precision ranging from 20.0% to 99.9%
Output Connector Banana Jacks 600V CAT II
Leader Cable Cable Assembly, 5 ft. (1.5m) 600 Volt CAT III, 95 Ohm
PHYSICAL
Size 2.41″H x 4.18″W x 9.03″L (6.12 x 10.61 x 22.94 cm)
Weight With batteries: 1 lb 9 oz (862 g)
Power Totex battery pack, with four LIO Rechargeable Cells.
Run with wall power down to 4V.
Batteries will charge when input voltage is greater than 10V.
Battery Life Battery Pack, full charge of 5000mAH
Operating at static screen, or occasional static test: 27 hours
Dynamic Operation : 17 hours
Low power : 71 hours
ENVIRONMENT
Altitude 6,500 ft (2,000 m)
Temperature Operating: (-10 if standard crystal) -20 to 70°C);
Storage:? (-30 to 80°C)
Humidity 10 to 90% non-condensing
GENERAL
Warranty 1 year
Safety Compliances Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 No 61010-1-04, UL 6101B (2003) and IEC/EN 61010-1 2nd Edition for measurement Category III, 600 V, EMC EN61326-1
Enclosure High-strength PC/ABS plastic with V0 rating with boot

 

 

Location